10 Supplement

VEGACAL 67 • Profibus PA

31759-EN-130917

pF

%

Lin%

Min-Max

adjustment

Linearization

PROFIBUS PA-output

Primary

Value

Secondary

Value 2

Secondary

Value 1

Target

Mode

Failure

mode

Alarms

Scaling

Source for

scaling

t

i

Damping

Sensor

characteristics

PA-Out

TB

FB

Select additional cyclic

value

Fig. 21: VEGACAL 67: Block diagram with AI (PA-OUT) value and additional cyclical value
TB Transducer Block

FB Function Block

Module of the PA sensors

For the cyclic data traffic, VEGACAL 67 provides the following modules:

AI (PA-OUT)

– PA-OUT value of the FB1 after scaling

Additional Cyclic Value

– Additional cyclical value (depending on the source)

Free Place

– This module must be used if a value should not be used in the data telegram of the cyclical

data traffic (e.g. replacement of the Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.

Note:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tel-

egram is structured.
Example 1 (standard setting) with distance value and additional cyclical value:

AI (PA-OUT)

Additional Cyclic Value