10 Supplement

VEGACAL 67 • Profibus PA

31759-EN-130917

Supporting tube length L1

0.2 … 5.6 m (0.656 … 18.37 ft)

Max. lateral load

10 Nm (7.4 lbf ft)

Max. tensile load (cable)

Ʋ Ceramic partly insulated: ø 8 mm

(0.315 in)

10 KN (2248 lbf)

Max. torque (process fitting - thread)

80 Nm (58 lbf ft)

Output variable
Output signal

digital output signal, format according to IEEE-754

Sensor address

126 (default setting)

Current value

10 mA, ±0.5 mA

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable
Measured variable

level of non-conductive liquids and solids

Measuring principle

phase-selective admittance processing (PSA)

Measuring range

0 … 3000 pF

Measuring frequency

270 kHz

Accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Temperature error

Ʋ < 120 pF

< 1 pF

Ʋ > 120 pF

1 % of the current measured value

Linearity error

< 0.25 % of the complete measuring range

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

-1 … 16 bar/-100 … 1600 kPa (-14.5 … 232 psig)

Process temperature (thread or flange temperature)

Ʋ Standard

-50 … +300 °C (-58 … +572 °F)

Ʋ with external housing

-50 … +400 °C (-58 … +752 °F)