6 Set up with the display and adjustment module PLICSCOM

VEGACAL 67 • Profibus PA

31759-EN-130917

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A linearisation is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. in a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearisation curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. By activating the appropriate curve, the

volume percentage of the vessel is displayed correctly. If the volume

should not be displayed in percent but e.g. in l or kg, a scaling can be

also set in the menu item "Display".

Linearization curve

Linear

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

In this menu item you can enter an unambiguous designation for the

sensor, e.g. the measurement loop name or the tank or product des-

ignation. In digital systems and in the documentation of larger plants,

a singular designation should be entered for exact identification of

individual measuring points.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you can

now jump to the main menu with the [ESC] key.

Additional adjustment and diagnosis options such as e.g. scaling,

simulation or trend curve presentation are shown in the following

menu schematic. You will find a detailed description of these menu

items in the operating instructions manual "Display and adjustment

module".
Basic adjustment

If the function "Reset" is carried out, the sensor resets all settings to

default.
The following values will be reset:

Function

Reset value

Max. adjustment

3000 pF

Min. adjustment

0 pF

Damping ti

0 s

Linearization

Linear

Sensor-TAG

Sensor

Linearization curve

Sensor-TAG

Optional settings

Reset