Application

Liquid

Standard
(DK ≥ 2)

Depending on the dielectric figure (dielectri value or ε

r

), measured

products can have a different reflective property. Therefore an
additional selection possibility is available.

Under "Sensitivity" you can select "Standard (DK ≥ 2)" or "Increased
sensitivity (DK < 2)
".

Through this the sensor is optimally adapted to the product and
measurement reliability, particularly in products with bad reflective
properties, is considerably increased.

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

To suppress fluctuations in the measured value display, e. g. caused
by an agitated product surface, a damping can be set. This time can
be between 0 and 999 seconds. Keep in mind that the reaction time of
the entire measurement will then be longer and the sensor will react to
measured value changes with a delay. In general, a period of a few
seconds is sufficient to smooth the measured value display.

Damping

0

s

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

High sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections can
be detected.

Gating out of false signals

Change now?

Proceed as follows:

Damping

Gating out of false sig-
nals

30

VEGAFLEX

62 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM