If possible, avoid sockets. Mount the sensor flush with the vessel top. If
this is not possible, use short sockets with small diameter.

Higher sockets or sockets with a bigger diameter can generally be
used. They simply increase the upper dead band. Check if this is
relevant for your measurement.

In such cases, always carry out a gating out of false signals after
installation. You can find further information under "Setup procedure".

h

d

d

h

DN40 ... DN150

£ 150

> DN150 ... DN200

£ 100

Fig. 8: Mounting socket

When welding the socket, make sure that the socket is flush to the
vessel wall.

1

2

Fig. 9: Socket must be installed flush

1

Unfavourable installation

2

Socket flush - optimum installation

Socket