Input variable
Nominal range
Overload resistance
Vacuum resistance
Gauge pressure
0 … 0.1
bar/0 … 10 kPa
15
bar/1500 kPa
-0.2
bar/-20 kPa
0 … 0.25
bar/0 … 25 kPa
30
bar/3000 kPa
-0.8
bar/-80 kPa
0 … 0.4
bar/0 … 40 kPa
30
bar/3000 kPa
-0.8
bar/-80 kPa
0 … 0.6
bar/0 … 60 kPa
35
bar/3500 kPa
-1
bar/-100 kPa
0 … 1
bar/0 … 100 kPa
35
bar/3500 kPa
-1
bar/-100 kPa
0 … 1.6
bar/0 … 160 kPa
50
bar/5000 kPa
-1
bar/-100 kPa
0 … 4
bar/0 … 40 kPa
65
bar/6500 kPa
-1
bar/-100 kPa
0 … 6
bar/0 … 600 kPa
90
bar/9000 kPa
-1
bar/-100 kPa
0 … 10
bar/0 … 1000 kPa
90
bar/9000 kPa
-1
bar/-100 kPa
0 … 16
bar/0 … 1.6 MPa
130
bar/13 MPa
-1
bar/-100 kPa
Absolute pressure
0 … 10
bar/0 … 1 MPa
90
bar/9 MPa
Accuracy (similar to DIN 16086 and IEC 770)
Reference conditions according to IEC 770
-
Temperature
18 … 30 °C
-
Relative humidity
45 … 75 %
-
Air pressure
860 … 1060
mbar
Determination of characteristics
limit point adjustment according to DIN 16086
Characterstic curve
Linear
Deviation determined according to the limit point method according to IEC 60770
1
Deviation
<
0.5 %
Influence of the ambient temperature
2
Average temperature coefficient of the zero signal
<
0.15 %/10 K
Long-term stability (similar to DIN 16086, DINV 19259-1 and IEC 60770-1)
Long-term drift of the zero signal
3
<
0.1 %/2
years
Ambient conditions
Ambient temperature
-20 … +85 °C
Storage and transport temperature
-40 … +100 °C
VEGABAR S 16
23