VEGA VEGASWING 63 - two-wire User Manual
Page 21
21
6 Setup
VEGASWING 63 • - two-wire
29232-EN-130409
There are the following possibilities to carry out the recurring function
test:
1. Filling of the vessel up to the switching point
2. Dismounting of the sensor and immersion in the the original prod-
uct
3. Short interruption of the supply line to the sensor
4. Pushing the test key on the signal conditioning instrument
1 Filling the vessel up to the switching point
If this does not cause any problems, you can fill the vessel up to the
switching point and monitor the correct sensor reaction.
2 Dismounting of the sensor and immersion in the original
product
You can dismount the sensor for test purposes and check its proper
functioning by immersing it in the original product.
3 Short interruption of the supply line to the sensor
The recurring function test according to IEC 61508 can be carried
out through a short interruption (> 2 seconds) of the supply line to the
sensor. This starts a test sequence.
The correctness of the subsequent switching conditions on the indi-
cations of the SPLC must be monitored. The sensor must neither be
dismounted nor triggered by filling the vessel.
You can carry out the function test with the outputted current values
also directly via a safety PLC or a process control system.
4 Pushing the test key on the signal conditioning instrument
A test key is lowered in the front plate of the signal conditioning instru-
ment. Push the test key for > 2 seconds with a suitable object. Hence
a test is started. Hence the correctness of the subsequent switching
conditions must be monitored via the two LEDs on the signal condi-
tioning instrument as well as the connected facilities. The sensor must
neither be dismounted, nor controlled by filling the vessel.
This test is valid if you cannot change the vessel filling or cannot
dismount the sensor.
The recurring function test according to IEC 61508 can be carried out
by pushing the test key on a respective signal conditioning instrument
or briefly (> 2 seconds) interrupting the supply line to the sensor.
The correctness of the subsequent switching conditions must be
monitored via the two LEDs on the signal conditioning instrument as
well as the connected devices. The sensor must neither be dismount-
ed nor triggered by filling the vessel.
This applies for VEGASWING 63 with two-wire electronics module
SWE60Z.
You can carry out the function test with the outputted current values
also directly via a safety PLC or a process control system.
A function test can be carried out with measurement setups in con-
junction with the two-wire electronics module SWE60Z EX.
Implementation - Func-
tion test
Test without filling or
dismounting the sensor
(3, 4)