VEGA VEGASON 64 Foundation Fieldbus User Manual
Page 56
-
Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1
(Online), the 'Cal_point_lo' is automatically set to the current sensor value. The unit is defined in
'L
evel_unit'
l
CAL_TYPE
-
Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value. Online:
current sensor value determines 'Cal_point_hi/lo'
l
level
-
Value after min./max.-adjustment
l
level_unit
-
Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'
l
level_offset
-
Offset that is added to the 'Level' value. Unit derives from 'Level_unit'
l
SENSOR_OFFSET
-
Offset that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'
l
end_of_operation_range
-
Set up to suit the process conditions
l
begin_of_operation_range
-
Set up to suit the process conditions
l
product_type
-
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
l
liquids_medium_type
-
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
l
solids_medium_type
-
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
l
liquids_vessel_type
-
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
l
solids_vessel_type
-
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
l
fast_level_change
-
Set up to suit the process conditions. If Special-Parameter adjustment has been utilized this
parameter cannot be written
l
first_echo_factor
-
Set up to suit the process conditions
l
pulse_velocity_correction
-
Set up to suit the process conditions
l
echo_quality
-
Signal/Noise ratio
l
empty_vessel_curve_corr_dist
56
VEGASON
64 • Foundation Fieldbus