VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 49
Error
Cause
Removal
Measured value
on the indicating
and adjustment
module does not
correspond to the
value in the PLC
The menu item
"
Display - Dis-
play value
"
is
not set to "
AI-
Out
"
Check values and correct, if neces-
sary
Instrument does
not appear during
connection setup
Profibus DP cab-
le pole-reversed
Check cable and correct, if necessary
Incorrect termina-
tion
Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification
Instrument not
connected to the
segment
Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or
wrong parameter adjustment
?
E
017
l
Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E
036
l
no operable sensor software
à Carry out a software update or send instrument for repair
?
E
041, E042, E043
l
Hardware error, electronics defective
à Exchange the instrument or send it in for repair
?
E
113
l
Communication conflict
à Exchange the instrument or send it in for repair
Fault messages via the
indicating/adjustment
module
VEGAPULS
61 • Foundation Fieldbus
49