4 setup procedure – VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 37
6
.4 Setup procedure
After VEGAPULS 61 is connected to voltage supply or after voltage
recurrence, the instrument carries out a self-check for approx. 30
seconds. The following steps are carried out:
l
Internal check of the electronics
l
Indication of the instrument type, the firmware as well as the
sensor TAGs (sensor designation)
l
Status byte goes briefly to fault value
Then the current measured value will be displayed and the
corresponding digital output signal will be outputted to the cable.
2)
As VEGAPULS 61 is a distance measuring instrument, the distance
from the sensor to the product surface is measured. To have the real
product level displayed, an allocation of the measured distance to the
percentage height must be made. To carry out this adjustment, the
distance is entered with full and empty vessel. If these values are not
known, an adjustment with the distance values, e.g. 10 % and 90 % is
also possible. Starting point for these distance specifications is always
the seal surface of the thread or flange. With these settings, the real
level is calculated. Furthermore the operating range of the sensor is
limited from maximum to the required range.
The real product level during this adjustment is not important, because
the min./max. adjustment is always carried out without changing the
product level. These settings can be made ahead of time without the
instrument having to be installed.
Caution:
If there is a separation of liquids with different dielectric values in the
vessel, e.g. from condensation, VEGAPULS 61 can detect under
certain circumstances only the medium with the higher dielectric value.
Keep in mind that interfaces can cause faulty measurements.
If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially
designed for interface measurement.
In the main menu item "Basic adjustment", the individual submenu
items should be selected one after the other and provided with the
correct parameter values.
Start your parameter adjustment with the following menu items of the
basic adjustment:
Proceed as follows:
2)
The values correspond to the actual measured level as well as to the set-
tings already carried out, e.g. default setting.
Switch on phase
Parameter adjustment
Carrying out min. ad-
justment
VEGAPULS
61 • Foundation Fieldbus
37
6 Set up with the indicating and adjustment module PLICSCOM
28449
-
EN
-100426