beautypg.com

VEGA VEGASON 63 Foundation Fieldbus User Manual

Page 41

background image

41

10 Supplement

VEGASON 63 • Foundation Fieldbus

28792-EN-130417

Reference conditions to measuring accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

Ʋ Reflector

ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)

Ʋ False reflections

Biggest false signal, 20 dB smaller than the useful signal

Measuring characteristics
Ultrasonic frequency

35 kHz

Interval

> 2 s (dependent on the parameter adjustment)

Abstrahlwinkel at -3 dB

Adjustment time

5)

> 3 s (dependent on the parameter adjustment)

Measuring accuracy
Resolution, general

> 1 mm (0.039 in)

Deviation

6)

see diagram

15 m

(49.213 ft)

8 m

(26.247 ft)

6 m

(19.685 ft)

12 m

(39.37 ft)

10 m

(32.808 ft)

3 m (9.843 ft)

10 mm (0.394 in)

20 mm (0.787 in)

30 mm (1.181 in)

6 mm (0.236 in)

-6 mm (-0.236 in)

-10 mm (-0.394 in)

-20 mm (-0.787 in)

-30 mm (-1.181 in)

Fig. 28: Deviation VEGASON 63

Influence of the ambient temperature to the sensor electronics

7)

Average temperature coefficient of the

zero signal (temperature error)

0.06 %/10 K

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

5)

Time to output the correct level (with max. 10 % deviation) after a sudden level change.

6)

Incl. non-linearity, hysteresis and non-repeatability.

7)

Relating to the nominal measuring range.