beautypg.com

VEGA VEGASON 63 Foundation Fieldbus User Manual

Page 27

background image

27

6 Set up with the display and adjustment module PLICSCOM

VEGASON 63 • Foundation Fieldbus

28792-EN-130417

2. Select the menu item "Basic adjustment" with [->] and confirm

with [OK]. Now the menu item "Min. adjustment" is displayed.

Min. adjustment
0.00 %
=
5.000 m(d)

4.000 m(d)

3. Prepare the % value for editing with [OK] and set the cursor to the

requested position with [->]. Set the requested percentage value

with [+] and save with [OK]. The cursor jumps now to the distance

value.

4. Enter the suitable distance value in m for the empty vessel (e.g.

distance from the sensor to the vessel bottom) corresponding to

the percentage value.

5. Save the settings with [OK] and move to "Max. adjustment" with

[->].

Proceed as follows:

Max. adjustment
100.00 %
=
1.000 m(d)

2.000 m(d)

1. Prepare the % value for editing with [OK] and set the cursor to the

requested position with [->]. Set the requested percentage value

with [+] and save with [OK]. The cursor jumps now to the distance

value.

2. Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. Keep in mind that the max.

level must lie below the dead band.

3. Save the settings with [OK] and move to "Medium selection" with

[->].

Each product has different reflective properties. In addition, there

are various interfering factors which have to be taken into account:

agitated product surfaces and foam generation (with liquids); dust

generation, material cones and echoes from the vessel wall (with

solids). To adapt the sensor to these different conditions, you should

first select "Liquid" or "Solid".

Medium

Liquid

With solids, you can also choose between "Powder/Dust", "Granular/

Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted perfectly to

the product and measurement reliability, particularly in products with

poor reflective properties, is considerably increased.
Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

Carry out max. adjust-

ment

Medium selection