10 supplement, 1 technical data – VEGA VEGASON 63 Foundation Fieldbus User Manual
Page 40
40
10 Supplement
VEGASON 63 • Foundation Fieldbus
28792-EN-130417
10 Supplement
10.1 Technical data
General data
Materials, wetted parts
Ʋ Process fitting
UP (glass-fibre reinforced polyester resin)
Ʋ Transducer diaphragm
316Ti
Ʋ Seal transducer diaphragm/process
fitting
EPDM
Materials, non-wetted parts
Ʋ Mounting strap
1.4301
Ʋ Compression flange
PPH, 316L
Ʋ Housing
Plastic PBT (polyester), Alu die-casting powder-coated,
316L
Ʋ Seal between housing and housing
cover
NBR (stainless steel housing), silicone (Alu/plastic hous-
ing)
Ʋ Inspection window in housing cover
Polycarbonate
Ʋ Ground terminal
316Ti/316L
Weight
2.7 … 5.7 kg (6 … 12.6 lbs), depending on the process
fitting and housing
Output variable
Output
Ʋ Signal
digital output signal, Foundation Fieldbus protocol
Ʋ Physical layer
according to IEC 61158-2
Cycle time
min. 1 s (dependent on the parameter setting)
Ʋ Damping (63 % of the input variable) 0 … 999 s, adjustable
Ʋ Met NAMUR recommendation
NE 43
Channel Numbers
Ʋ Channel 1
Primary value
Ʋ Channel 2
Secondary value 1
Ʋ Channel 3
Secondary value 2
Transmission rate
31.25 Kbit/s
Current value
10 mA, ±0.5 mA
Resolution, digital
> 1 mm (0.039 in)
Input variable
Measured variable
distance between lower edge of the transducer and
product surface
Measuring range
Ʋ Liquids
up to 15 m (49.21 ft)
Ʋ Bulk solids
up to 7 m (22.97 ft)
Dead band