6 Setup
VEGASWING 63 • - Relay (DPDT)
29229-EN-130409
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
With plastic housings, the switching condition of the electronics can
be checked when the housing cover is closed (control lamp). With the
basic setting, products with a density > 0.7 g/cm³ (0.025 lbs/in³) can
be detected. For products with lower density, the switch must be set
to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating and
adjustment elements:
•
Signal lamp (1)
•
DIL switch for mode adjustment - A/B (2)
•
DIL switch for sensitivity adjustment (3)
Note:
For test purposes, immerse the tuning fork of VEGASWING 63 always
in liquids. Do not test the function of VEGASWING 63 with your hand.
This can damage the sensor.
6.2 Adjustment elements
1
2
3
4
5
6
7
8
1
2
3
Fig. 13: Oscillator SWE60R - Relay output
1 Signal lamp (LED)
2 DIL switch for mode adjustment
3 DIL switch for sensitivity adjustment
Control lamp for indication of the switching status
•
green = relay energized
•
red = relay deenergized
•
red (flashing) = failure
With the mode adjustment (A/B) you can change the switching
condition of the relay. You can set the required mode according to the
Function/Configuration
Signal lamp (1)
Mode adjustment (2)