5 Connecting to power supply
VEGASWING 63 • - Relay (DPDT)
29229-EN-130409
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10. Screw the housing cover back on
The electrical connection is hence finished.
5.3 Wiring plan, single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d
version.
1
4
4
4
2
3
Fig. 10: Material versions, single chamber housing
1 Plastic (not with Ex d)
2 Aluminium
3 Stainless steel (not with Ex d)
4 Filter element for pressure compensation (not with Ex d)
3
5
1
2
4
R
20-253V AC
20-72V DC
A
B
L
N
1 2
3 4 5 6 7 8
0,5 g / cm3
0,7 g / cm3
3 4 5 6 7 8
+
Fig. 11: Electronics and connection compartment, single chamber housing
1 Control lamp
2 DIL switch for mode adjustment
3 DIL switch for switching point adaptation
4 Ground terminal
5 Connection terminals
We recommend connecting VEGASWING 63 in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe condition).
Housing overview
Electronics and connec-
tion compartment
Wiring plan