beautypg.com

VEGA VEGASCAN 850 Profibus DP signal output User Manual

Page 12

background image

12

Profibus DP signal output VEGASCAN 850

VEGASCAN writes the following answer telegram into the 6 Byte inputs of the Profibus master:

6 Byte

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Status

High-Word

Low-Word

Add. info

0xYY

1...60

0x00

0x00

0xHH

0xLL

PC/DCS

number

PC/DCS measured value

Format of the VEGASCAN answer

Status:

0x00 =

valid measured value

0x80 =

old measured value (probably con-
nection interrupted)

0xFE = no PC/DCS value available (not

configured)

0xFF =

general error

PC/DCS measured value

0xHH = High-Byte of the measured value
0xLL =

Low-Byte of the measured value

Value range comprises max. +32768 to
-32767.

Data image in VEGASCAN 850

Measured value image in mode 6E6A

In this operating mode, the PC/DCS values can be read out individually in VEGASCAN, i.e. the
Profibus master requests a measured value and this measured value is delivered by
VEGASCAN.

Control command 0xCD

When enquiring with this control command, VEGASCAN answers with an individual PC/DCS
value. The enquiry telegram written by the Profibus master into the 6 byte outputs is struc-
tured as follows.

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Control

command

reserved

PC/DCS

number

reserved

reserved

reserved

0xCD

1...60

0xFF

0xFF

0xFF

0xFF

6 Byte

Format of the enquiry acc. to single PC/DCS values