Profibus DP signal output VEGASCAN 850
VEGASCAN writes the following answer telegram into the 6 Byte inputs of the Profibus master:
6 Byte
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Status
High-Word
Low-Word
Add. info
0xYY
1...60
0x00
0x00
0xHH
0xLL
PC/DCS
number
PC/DCS measured value
Format of the VEGASCAN answer
Status:
0x00 =
valid measured value
0x80 =
old measured value (probably con-
nection interrupted)
0xFE = no PC/DCS value available (not
configured)
0xFF =
general error
PC/DCS measured value
0xHH = High-Byte of the measured value
0xLL =
Low-Byte of the measured value
Value range comprises max. +32768 to
-32767.
Data image in VEGASCAN 850
Measured value image in mode 6E6A
In this operating mode, the PC/DCS values can be read out individually in VEGASCAN, i.e. the
Profibus master requests a measured value and this measured value is delivered by
VEGASCAN.
Control command 0xCD
When enquiring with this control command, VEGASCAN answers with an individual PC/DCS
value. The enquiry telegram written by the Profibus master into the 6 byte outputs is struc-
tured as follows.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Control
command
reserved
PC/DCS
number
reserved
reserved
reserved
0xCD
1...60
0xFF
0xFF
0xFF
0xFF
6 Byte
Format of the enquiry acc. to single PC/DCS values