Profibus DP signal output VEGASCAN 850

Grouping of measured values acc. to PC/DCS output number

Block no.

PC/DCS output no.

1

1...8

2

9...16

3

17...24

4

25...32

5

33...40

6

41...48

7

49...56

8

57...60

Example:
Enquiry telegram to VEGASCAN 850 (2 bytes):

0xCC 0x01

Block no. 1 is enquired

Answer telegram from VEGASCAN 850 (50 Byte):

0xCC 0x00 0x01 0xYY 0x00 0x00 0xHH 0xLL 0x02 0xYY 0x00 0x00 0xHH ...

Control word PC/DCS value no. 1 PC/DCS value no. 2

0xYY

= Index-Byte

0xHH

= High-Byte measured value

0xLL

= Low-Byte measured value

Data image in VEGASCAN 850

5.1 Measured value image

VEGASCAN 850 can administrate up to 60
measurement loops. For transfer of the meas-
ured values of a measurement loop,
VEGASCAN provides up to 60 PC/DCS out-
puts. One or several PC/DCS outputs with
individual index can be assigned to each of
these measurement loops. The configuration
of VEGASCAN is made with the VEGA ad-
justment software VVO (see chapter "2 PC/
DCS output in VEGASCAN“).

Measured value image in mode 50E2A

In this operating mode the PC/DCS values
are imaged in blocks (VEGASCAN) depend-
ing on the PC/DCS output number.

The assignment of the individual PC/DCS
values in blocks is shown as diagram. For
readout of the measured values from
VEGASCAN, the Profibus master has to send
a control command to VEGASCAN.

2 Byte

output range

Byte 1

Byte 2

Control

command

Block no.

0xCC

0x01

...0x08

Measured value enquiry of the Profibus master

Control command 0xCC:

When enquiring with this control command,
the PC/DCS values will be grouped in as-
cending sequence acc. to the PC/DCS out-
put number. The measured value image is
always sorted acc. to the PC/DCS output
number.

Enquiry of measured values:

DP master: Control command:0xCC
Block no.:

0x01...0x08

5 Data image in VEGASCAN 850