Nominal range
Overload, max. pressure Overload, min. pressure
0 … 900
psi
2900
psi
0
psi
Reference conditions and actuating variables (similar to DIN EN 60770-1)
R
eference conditions according to DIN EN 61298-1
-
T
emperature
+
15 … +25 °C (+59 … +77 °F)
-
R
elative humidity
45 … 75 %
-
A
ir pressure
860 … 1060
mbar/86 … 106 kPa (12.5 … 15.4 psig)
D
etermination of characteristics
L
imit point adjustment according to IEC 61298-2
C
haracteristics
linear
R
eference installation position
upright, diaphragm points downward
I
nfluence of the installation position
<
0.2
mbar/20 Pa (0.003 psig)
Deviation determined according to the limit point method according to IEC 60770
9)
A
pplies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue
current output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) is the relation
nominal measuring range/set span.
D
eviation
-
T
urn down 1 : 1 up to 5 : 1
<
0.075 %
-
T
urn down > 5 : 1
<
0.015 %
x TD
D
eviation with absolutely flush process fittings EV, FT
-
T
urn down 1 : 1 up to 5 : 1
<
0.05 %
-
T
urn down > 5 : 1
<
0.01 %
x TD
D
eviation with absolute pressure measuring range 0.1 bar
-
T
urn down 1 : 1 up to 5 : 1
<
0.25 %
x TD
-
T
urn down > 5 : 1
<
0.05 %
x TD
Influence of the product or ambient temperature
A
pplies also to instruments with analogue 4 … 20 mA current output and refers to the set span.
T
hermal change zero signal and output span, reference temperature 20 °C (68 °F):
-
I
n the compensated temperature range
0 … +100 °C (+32 … +212 °F)
< (0.05 % + 0.1 %
x TD)
-
O
utside the compensated temperature
range
< (0.05 % + 0.15 %
x TD)
9)
I
ncl. non-linearity, hysteresis and non-repeatability.
VEGABAR
64 • 4 … 20
mA/HART
57
10 S
upplement
27525
-
EN
-081209