beautypg.com

VEGA VEGABAR 64 4 … 20 mA_HART User Manual

Page 57

background image

Nominal range

Overload, max. pressure Overload, min. pressure

0 … 900

psi

2900

psi

0

psi

Reference conditions and actuating variables (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

15 … +25 °C (+59 … +77 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

D

etermination of characteristics

L

imit point adjustment according to IEC 61298-2

C

haracteristics

linear

R

eference installation position

upright, diaphragm points downward

I

nfluence of the installation position

<

0.2

mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

9)

A

pplies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue

current output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) is the relation
nominal measuring range/set span.

D

eviation

-

T

urn down 1 : 1 up to 5 : 1

<

0.075 %

-

T

urn down > 5 : 1

<

0.015 %

x TD

D

eviation with absolutely flush process fittings EV, FT

-

T

urn down 1 : 1 up to 5 : 1

<

0.05 %

-

T

urn down > 5 : 1

<

0.01 %

x TD

D

eviation with absolute pressure measuring range 0.1 bar

-

T

urn down 1 : 1 up to 5 : 1

<

0.25 %

x TD

-

T

urn down > 5 : 1

<

0.05 %

x TD

Influence of the product or ambient temperature
A

pplies also to instruments with analogue 4 … 20 mA current output and refers to the set span.

T

hermal change zero signal and output span, reference temperature 20 °C (68 °F):

-

I

n the compensated temperature range

0 … +100 °C (+32 … +212 °F)

< (0.05 % + 0.1 %

x TD)

-

O

utside the compensated temperature

range

< (0.05 % + 0.15 %

x TD)

9)

I

ncl. non-linearity, hysteresis and non-repeatability.

VEGABAR

64 • 4 … 20

mA/HART

57

10 S

upplement

27525

-

EN

-081209