1
2
Fig. 4: Temperature ranges
1
Process temperature
2
Ambient temperature
4.2 Mounting steps
F
or mounting VEGABAR 64, a welded socket is required. You can find
these components in the supplementary instructions manual "Welded
socket and seals".
S
eal the thread with teflon, hemp or a similar resistant seal material on
the process fitting thread 1½ NPT.
à Screw VEGABAR 64 into the welded socket. Tighten the hexagon
on the process fitting with a suitable wrench. Wrench size, see
chapter "Dimensions".
Warning:
T
he housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
S
eal the flange connections according to DIN/ANSI with a suitable,
resistant seal and mount VEGABAR 64 with suitable screws.
U
se the seal suitable for the respective process fitting. You can find
the components in the supplementary instructions manual "Welded
socket and seals".
4.3 Mounting steps external housing
1
M
ark the holes according to the following drilling template
2
D
epending on the mounting surface, fasten the wall mounting
plate with 4 screws
Welding the socket
Sealing/Screwing in
threaded versions
Sealing/Screwing in
flange versions
Sealing/Screwing in hy-
gienic fittings
Wall mounting