5 diagnostics, 1 maintenance, 2 failure rectification – VEGA VEGABAR 40 Profibus PA User Manual
Page 29: Fault signals, Troubleshooting
VEGABAR 40 (Profibus PA)
29
Diagnostics
5 Diagnostics
5.1 Maintenance
VEGABAR process pressure transmitters are
maintenance-free.
5.2 Failure rectification
Fault signals
VEGABAR provides maximum reliability
trough its self-test and continuous self-moni-
toring. If however malfunctions occur, VEGA-
BAR diagnosis distinguishes between atypi-
cal process conditions and faults in the
VEGABAR.
Atypical process conditions
Exceeding or falling short of measuring
range limits (fault signal extinguishes when
the measured value is again in the measuring
range).
Failure in VEGABAR
Failure in the electronics, interference or
damage in the measuring cell.
The following table assists in analysis of fault
signals.
Reason
Fault signal via
DOT-matrix
Bar graph
Digital indication
Clearly
"OPERATE
Bar graph 0 %
outside
????
or 100 %
measuring
bar“,
digital value
range
no more
flashes, tendency
adjustment
indication
possible
active
Overload
Bar graph 0 %
range
or 100 %,
of the
for digital value
meas. cell
four segments
flash
Failure in
all segments
VEGABAR
flash
On instruments with menu-driven adjustment
with additional functions, the possible rea-
sons are displayed under the menu item
"Diagnosis-no.“ in case of failure.
Diagnosis-no.
Meaning
1
No frequency from C/f-converter
2
Frequency signal of the capacitor not
within the limit values
3
Frequency signal of the reference
capacitor not within the limit values
4
Frequency signal temperature not
within the limit values
7
Communication with EEPROM dis-
rupted
9
Error in EEPROM CRC-checksum
11
Process connection or electronics
module has been exchanged (ap-
pears for approx. 20 s after switching
on for the first time after exchange)
Troubleshooting
If the displayed value does not correspond
to the level in the vessel or to the process
pressure, the following measures must be
taken:
- check the pressure compensation (only
with gauge pressure measuring ranges)
- check the electrical connection.
Checking pressure compensation
Open the housing of VEGABAR. The meas-
ured value must not change. However if the
displayed value changes, compensation of
the atmospheric pressure is not ensured and
will lead to distortion of the measured value.
Check the breather on the VEGABAR hous-
ing.