Function
ground

2.2 Connection diagram

Electrical connection

Plug connec-
tion

Display module

VEGADIS 10 with display module

2 Electrical connection

2.1 Connection instructions

The electronics in VEGABAR 40 requires a
supply voltage of 9 … 32 V DC. The supply
voltage and the digital output signal are lead
via the same two-wire connection cable to the
terminals. The external energy is provided
via a segment coupler.

Note the following instructions for electrical
connection:
- Connection must be made according to the

specific installation standards (e.g. in Ger-
many acc. to the VDE-regulations).

- Electrical connection must have a protec-

tive measure against polarity reversal.

- The connection of field instruments is gen-

erally made via T-adapters on stubs.

- Screened cable is recommended for con-

nection (cable types see chapter "1.3 Tech-
nical data“). The shielding must be
grounded on both ends (on the T-adapter
and on VEGABAR).

- For use in Ex areas, the installation regula-

tions must be observed.

Stub

T-adapter

Bus cable