beautypg.com

3 mounting, 1 mounting instructions, 2 compensation of the atmospheric pressure – VEGA D98 Pressure transmitter User Manual

Page 7

background image

Pressure transmitter D98

7

Mounting

3 Mounting

3.1 Mounting instructions

Cable entry

The pressure transmitter can be mounted in
any position.

Cable entries must point downward to avoid
moisture ingress. For this purpose, the hous-
ing can be rotated by 330 °. With vertically
mounted sensors, the connection cable to the
housing must point downward so that rain
and condensed water can drip off. This ap-
plies especially to outdoor mounting, or
mounting in humid rooms (e.g. caused by
cleaning processes) or on cooled or heated
vessels.

Moisture

3.2 Compensation of the atmos-

pheric pressure

The atmospheric pressure is compensated
via a breather facility integrated in the hous-
ing (air-permeable and moisture-resistant
PTFE insert).