Pressure transmitter D98
Technical data
Power supply and signal circuit
Power supply
- without indication
12 … 36 V DC
Residual ripple of the power supply
no influence with U
SS
≤
1 V
Output signal
4 … 20 mA (factory setting)
Current limitation
approx. 22 mA
Fault signal
approx. 22 mA
Average delay time
20 ms
Max. permissible load
see load diagram:
12
300
600
900
18
24
30
36
load in
Ω
supply voltage
in V
2 Technical data
2.1 Data
Nominal measuring range
Gauge pressure resistanLow pressure resistance
Gauge pressure
0…0.4 bar / 0…40 kPa
30 bar / 3 000 kPa
-0.8 bar / -80 kPa
0…1.0 bar / 0…100 kPa
35 bar / 3 500 kPa
-1.0 bar / -100 kPa
0…2.5 bar / 0…250 kPa
50 bar / 5 000 kPa
-1.0 bar / -100 kPa
0…4.0 bar / 0…400 kPa
65 bar / 6 500 kPa
-1.0 bar / -100 kPa
0…10.0 bar / 0…1 000 kPa
90 bar / 9 000 kPa
-1.0 bar / -100 kPa
0…16.0 bar / 0…1 600 kPa
130 bar / 13 000 kPa
-1.0 bar / -100 kPa
Measuring accuracy (according to DIN 16 086, DIN V 19 259-1 and IEC 770)
Measuring deviation
Reference conditions acc. to IEC 770, e.g.
- temperature
15°C … 35°C
- rel. humidity
45 % … 75 %
- air pressure
860 mbar … 1060 mbar
Determination of characteristics
limit point adjustment acc. to DIN 16 086
Characteristics
linear
Deviation in characteristics
1)
< 0.25 %
Hysteresis (repeatability)
1)
< 0.02 %
1)
Relating to the nominal range
2)
In compensated temperature range of 0°C … +80°C, reference temperature 20°C
3)
According to IEC 770, Punkt 6.3.2 related to the nominal range
4)
The use of a properly fitting cable seal in the cable connection is necessary for maintaining the housing
protection IP 66. If the seal used does not fit the cable, it should be replaced by a suitable one.
5)
FDA approved