beautypg.com

VEGA VEGATOR 532 Ex User Manual

Page 29

background image

Maximum values

-

U

B

36 V DC

-

I

B

60 mA

Transistor voltage loss (U

CE

)

approx. 1.5 V at I

B

60 mA

Inverse current (I

0

)

<

10 µA

Adjustment elements

DIL switch

for preadjustment of the mode

Potentiometer

for switching point adjustment

Control lamps in the front plate

-

Status indication operating voltage

Signal lamp green (LED)

-

Status indication fault signal

Signal lamp red (LED)

-

Status indication switching point control

Signal lamp yellow (LED)

Ambient conditions

Ambient temperature

-20 … +60 °C (-4 … +140 °F)

Storage and transport temperature

-40 … +70 °C (-40 … +158 °F)

Electromechanical data

Electrical connection

-

Carrier BGT 596 Ex

33-pole multipoint connector, series F (d, b, z) with
coding holes

-

Housing type 505 Ex

Screw terminal for wire cross-section up to 1.5 mm²
(AWG 16)

Electrical protective measures

Protection

-

Signal conditioning instrument - not
mounted

IP

00

-

mounted into BGT 596 Ex - front side
(completely equipped)

IP

30

-

mounted into BGT 596 Ex - upper and
lower side

IP

20

-

mounted into BGT 596 Ex - wiring side

IP

00

-

mounted into housing type 505 Ex

IP

30

Overvoltage category

II

Protection class

II

Approvals

1

)

ATEX

ATEX II (1) GD [EEx ia] IIC

1)

Deviating data in Ex applications: see separate safety instructions.

VEGATOR

532 Ex • Signal conditioning instrument

29

9 Supplement

23435

-EN

-090130