9 supplement, 1 technical data, 9supplement – VEGA VEGATOR 532 Ex User Manual
Page 28
9
Supplement
9
.1 Technical data
General data
Series
19" module card, multipoint connector according to
DIN
41612, including transparent cover (lockable)
Weight
150 g (5.3 oz)
Power supply
Operating voltage
20 … 53 V AC, 50/60 Hz, 20 … 72 V DC
Max. power consumption
2 W, 3 VA
Fuse
-
Supply area
T
1 A, 253 V
-
Switching off possibility
min. 35 A at 253 V AC or 125 V DC
Sensor input (channel)
Quantity
2 x level detection or 2 x two-point control (min./
max.)
Response resistor
1 … 200 kΩ adjustable
Parallel resistor for fault monitoring
220 kΩ
Measuring circuit
max. 5 V eff., max. 1 mA
Permissible line capacitance
1 x 100 nF or 2 x 70 nF with min./max. control
Switching hysteresis
15 %
Relay outputs
Quantity
2
Mode
A/B switch (A - max. detection or overfill protection,
B - min. detection or dry run protection) adjustable
separately for each channel
Damping
500 ms
Contact
1 spdt for each output
Contact material
AgNi, hard gold-plated
Turn-on voltage
≥
10 mV DC, ≤ 253 V AC/DC
Switching current
≥
10 µA DC, ≤ 3 A AC, 1 A DC
Breaking capacity
≤
750 VA, ≤ 54 W DC
Transistor outputs
Number, function
1 output, synchronously switching with the relay
Galvanic separation
Floating
28
VEGATOR
532 Ex • Signal conditioning instrument
9 Supplement
23435
-EN
-090130