4 exchanging the electronics module – VEGA VEGABAR 65 Profibus PA User Manual

Page 49

background image

F

Kl

=

0.075 %

F

perf

= √((0.05 % + 0.1 % x 1.25)

2

+ (0.075 %)

2

)

F

perf

=

0.19 %

Total deviation digital output signal in percent:
F

total

= F

perf

+ F

stab

F

stab

= (0.1 % x TD)/year

F

stab

= (0.1 % x 1.25)/year

F

stab

=

0.125 %

F

total

=

0.19 % + 0.125 % = 0.315 %

Total deviation digital output signal absolute:
F

total

=

0.315 % x 8 bar/100 % = 25.2 mbar

Basic accuracy analogue output signal in percent:
F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.05 % + 0.1 % x TD)

F

Kl

=

0.075 %

F

a

=

0.15 %

F

perf

= √((0.05 % + 0.1 % x 1.25)

2

+ (0.075 %)

2

+ (0.15 %)

2

)

F

perf

=

0.24 %

Total deviation analogue output signal in percent:
F

total

= F

perf

+ F

stab

F

stab

= (0.1 % x TD)/year

F

stab

= (0.1 % x 1.25)/year

F

stab

=

0.125 %

F

total

=

0.24 % + 0.125 % = 0.365 %

Total deviation analogue output signal absolute:
F

total

=

0.365 % x 8 bar/100 % = 29.2 mbar

8

.4 Exchanging the electronics module

In case of a defect, the electronics module can be exchanged by the
user against an identical type. If no electronics module is available on
side, the module can be ordered for the VEGA agency serving you.

Ordering and exchange are possible with or without sensor serial
number. The electronics module with serial number includes order-
specific
data such as factory setting, seal material etc. These are not
included in the electronics module without serial number.

The serial number is stated on the type label of VEGABAR 65 or on the
delivery note.

VEGABAR

65 • Profibus PA

49

8 Maintenance and fault rectification

28253

-

EN

-090522