5 Diagnosis
5.1 Simulation
To simulate a certain filling, you can call up the function "Simulation" on the adjustment module
MINICOM, in the software program VVO or in the HART
®
handheld. This function simulates a
certain current value. Please keep in mind that connected devices, such as e.g. a PLC, react
according to their settings and will probably activate alarms or system functions.
5.2 Failure rectification
Error
Corrective measure
E 013
Sensor does not find a
- Message is displayed during the warm-up
level echo
phase.
- If the message remains, the DK value of the
medium might be too low.
Check the useful level and noise level.
See "4.2 Adjustment with adjustment module
MINICOM; 6. Useful level and noise level".
If the message still remains, carry out a new
adjustment.
E 017
Adjustment span too small
Carry out the adjustment again. Make sure that
the difference between min. and max. adjust-
ment is at least 10 mm.
E 036
Software update incorrect
Return the instrument for repair.
E 040
Hardware failure/
Check all connection cables.
Electronics defective
Contact our service department.
Diagnosis