York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual
Page 45
Y
ORK INTERNA
TIONAL
45
FORM 160.49-O2
MON.
10:00 AM
Low Evap.
Low Evap.
54.3
54.4
To restart, press
See OPERATION
Pressure
Pressure
PSIG (R-22)
PSIG (R-22)
compressor switch
ANALYSIS Table 2
Transducer
25
25.1
from STOP/RESET
Symptom 2
(LEP)
PSIG (R-134a)
PSIG (R-134a)
to START position
MON.
10:00 AM
Low Evap.
LEP external
Set to Job
Set to Job
To restart, press
See OPERATION
Pressure
control (Brine
Spec.
Spec.
compressor switch
ANALYSIS Table 2
Brine
units only)
from STOP/RESET
Symptom 2.
to START position
MON.
10:00 AM
Low Oil
Low Oil
25
15
Will restart when
Refer to OPERATION
Pressure
Pressure
PSID
PSID
pressure increases
ANALYSIS Table 2
Transducer
to 25 PSID. To
Symptoms 4, 5, 6, 7,
(OP)
restart, press com-
9, 10, 11
pressor switch from
STOP/RESTART to
START position.
MON.
10:00 AM
High
High Pressure
265
205
Will restart when
See Operational
Pressure
Safety Control
PSIG (R-22)
PSIG (R-22)
Pressure falls to
Analysis Table 2
(HP)
180
120
205 PSIG. To restart
Symptom 1 High
PSIG (R-134a)
PSIG (R-134a)
press compressor
Discharge Pressure
switch from STOP/
RESET to START
position
MON.
10:00 AM
Evap. Trans.
Evap. Pressure
To restart press
Defective Evap. Pressure
or Probe
Transducer or
compressor switch
Transducer or Leaving
Error
Leaving Chilled
from STOP/RESET
Chilled Water thermistor
Water Thermis-
to START position
(RS1). LCWT minus satu-
tor (RS1)
ration temperature is less
than –2.5°F or greater than
25°F. Checked every 10
minutes following a 10 min.
bypass at start-up.
MON.
10:00 AM
Motor Con-
CM2 or Solid
Reset the device
CM2, or Solid State
troller – Ext.
State Starter
that caused the shut-
Starter has shutdown
Reset
(RT2)
down. Chiller will
chiller
start automatically.
MON.
10:00 AM
High
Discharge Temp.
220°F
219°F
To restart press
Condenser tubes dirty or
Discharge
Thermistor
compressor switch
scaled or high condenser
Temp.
(RT2)
from STOP/RESET
water temperature. (See
to START position.
Symptom 1, Table 1.)
MON.
10:00 AM
High Oil
Oil Temperature
170°F
169°F
To restart press
Dirty oil filter or restricted
Temp.
Thermistor
compressor switch
oil cooler line. Change oil
(RT3)
from STOP/RESET
filter. Refer to OPERATION
to START position
ANALYSIS Table 2,
Symptom 9.
MON.
10:00 AM
Power
Auto-Restart
Micro Board
8.29VDC
7.84VDC
Optional AUTO
Will restart automa-
Power Failure.
Failure
undervoltage
Restart Plug is
tically when voltage
circuit on 5V
installed on
reaches 8.29VDC.
unregulated
Micro Board
An undervoltage
supply
circuit on the Micro
Board monitors the
5VC unregulated
supply for an under-
voltage condition.
MON.
10:00 AM
Power
Micro Board
8.29VDC
7.84VDC
Auto restart plug
To restart, press
Power Failure
Failure
undervoltage
is removed on
compressor switch
circuit on 5V
Micro Board
to STOP-RESET
unregulated
Position and then to
supply
START position
(Continued on page 46)