beautypg.com

System starting & shutdown sequence, Condenser water temperature control – York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 32

background image

32

YORK INTERNATIONAL

However, the current draw (amperes) by the compres-
sor motor cannot exceed the setting of the % CUR-
RENT LIMIT
at any time during the unit operation, since
the MicroComputer Control Center 40 to 100% three-
phase peak current limit software function, plus the 3-
phase 100% solid state overload current limiter (CM-
2) on Electro-Mechanical Starter applications or the
Solid State Starter current Limit function will override
the temperature control function and prevent the Pre-
rotation Vanes from opening beyond the % CURRENT
LIMIT
setting.

If the load continues to decrease, after the Prerotation
Vanes are entirely closed, the chiller will be shut down
by the Low Water Temperature control (LWT) function
which is displayed on the Control Center as:

MON 10:30 AM – LOW WATER TEMPERATURE – AUTOSTART

This occurs when the leaving water temperature falls
to 4°F below setpoint or 36°F, whichever is higher. The
LWT is part of the Micro Board.

NOTE: If the temperature setpoint has been repro-

grammed within the last 10 minutes, the LWT
cutout is 36°F for 10 minutes.

Condenser Water Temperature Control

The YORK Millennium chiller is designed to use less
power by taking advantage of lower than design tem-
peratures that are naturally produced by cooling tow-
ers throughout the operating year. Exact control of con-
denser water such as a cooling tower bypass, is not
necessary for most installations. The chiller requires
only that the minimum condenser water temperature

SYSTEM STARTING & SHUTDOWN SEQUENCE

OPERATOR INITIATED

FIG. 15 – CHILLER STARTING SEQUENCE & SHUTDOWN SEQUENCE

NOTES: 1. REF. MICROBOARD PROGRAM JUMPER JP6

2. REF. MICROBOARD PROGRAM JUMPER JP4

(NOTE 2)

LD00952

This manual is related to the following products: