York BQ 036 User Manual
Page 26
036-21508-005-A-0305
26
Unitary Products Group
TABLE 15: ELECTRICAL DATA - BQ060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0
0.0
49.0
80
2CE04510506
4.0
19.2
73.1
100
2CE04510706
5.6
26.9
82.7
100
2CE04511006
8.0
38.5
97.1
110
2CE04511506
11.9
57.2
120.5
125
2CE04512006
15.9
76.4
144.6
150
2CE04513006
22.2
106.7
182.4
200
NONE 0.0
0.0
49.0
80
2CE04510506
5.3
22.1
76.6
100
2CE04510706
7.5
31.3
88.1
110
2CE04511006
10.6
44.2
104.2
125
2CE04511506
15.9
66.3
131.8
150
2CE04512006
21.2
88.3
159.4
175
2CE04513006
29.6
123.3
203.2
225
NONE 0.0
0.0
33.0
50
2CE04510525
2
4.0
11.1
46.9
60
2CE04510725
2
5.6
15.5
52.5
60
2CE04511025
8.0
22.2
60.8
70
2CE04511525
11.9
33.0
74.3
80
2CE04512025
15.9
44.1
88.2
90
2CE04513025
22.2
61.6
110.1
125
NONE 0.0
0.0
33.0
50
2CE04510525
2
5.3
12.7
49.0
60
2CE04510725
2
7.5
18.0
55.6
70
2CE04511025
10.6
25.5
64.9
70
2CE04511525
15.9
38.2
80.8
90
2CE04512025
21.2
51.0
96.8
100
2CE04513025
29.6
71.2
122.0
125
NONE 0.0
0.0
17.1
25
2CE04510746
2
6.8
8.2
27.3
35
2CE04511046
2
10.1
12.1
32.3
35
2CE04511546
2
13.6
16.4
37.5
40
2CE04512046
2
19.5
23.5
46.4
50
2CE04513046
2
28.8
34.6
60.4
70
NONE 0.0
0.0
13.6
20
2CE04511058
10.6
10.2
26.3
30
2CE04511558
15.9
15.3
32.7
35
2CE04512058
21.2
20.4
39.1
40
2CE04513058
30.4
29.3
50.1
60
ID Blower
Motor
FLA
Conv
Outlet
Amps
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Model
Tonnage
Voltage
Compressors
OD Fan
Motor
FLA
1.3
3.3
0.0
575-3-60
7.9
50
1.3
3.3
0.0
2.3
6.6
0.0
230-3-60
19.3
137
2.3
6.6
0.0
208-3-60
2.3
6.6
0.0
230-1-60
32.1
148
2.3
6.6
0.0
5
208-1-60
32.1
148
19.3
137
460-3-60
10.0
62
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.