The internal wiring harness furnished with this unit is an integral
part of a ETL and CGA design certified unit. Field alteration to
comply with electrical codes should not be required.

A fused disconnect switch should be field provided for the unit.
The switch must be separate from all other circuits. Wire entry
at knockout openings require conduit fittings to comply with
CEC (in Canada), NEC (in U.S.A.) and/or local codes. Refer to
the Dimensions and Clearances Figure for installation location.
If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram and the same minimum gauge as the replaced wire.

Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.

CAUTION: When connecting electrical power and control

wiring to the unit, waterproof type connectors

MUST BE USED so that water or moisture cannot
be drawn into the unit during normal operation. The
above waterproofing conditions will also apply
when installing a field-supplied disconnect switch.

FIG. 5 - TYPICAL FIELD WIRING

Wire Size

1

AWG. Gauge

22

20

19

18

16

40

120

150

190

305

Maximum Wire Length

2

Feet

Notes:

1. Solid, Class II copper wire

2. Based on a voltage drop of 1.2 volts per wire.

3. Total wire length is from unit to room thermostat, and back to unit

TABLE 2 - CONTROL WIRE SIZES

511.06-N3Y