TABLE 6 - SUPPLY AIR BLOWER PERFORMANCE (15 TON)

180 MBH - BOTTOM DUCT CONNECTIONS

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

CFM

4500

5250

6000

6750

7200

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE

850

6.0**

0.9

2.4

2.2

0.7

3.0

2.7

0.5

3.2

2.9

-

-

-

-

-

-

870

5.5

1.0

2.5

2.3

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

-

-

-

915

4.5

1.1

2.6

2.4

0.9

3.4

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

3.5

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

4.9

4.4

980

3.0

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1010

2.0

1.4

3.1

2.8

1.2

3.8

3.4

1.0

4.2

3.8

0.7

5.0

4.5

0.6

5.4

4.8

1040

1.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.2

4.7

0.7

5.7

5.1

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

965

6.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

5.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1025

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.8

5.1

4.6

0.7

5.6

5.0

1065

3.5

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

1095

3.0

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

-

-

-

1130

2.0

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

-

-

-

-

-

-

1170

1.0

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE

870

6.0**

1.0

2.4

2.2

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

-

-

-

915

5.0

1.1

2.6

2.4

0.9

3.3

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

4.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

3.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

2.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

1.0

1.6

3.3

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY

980

6.0

1.3

2.9

2.6

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

4.0

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

-

-

-

1095

3.5

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

-

-

-

1130

2.5

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

-

-

-

-

-

-

1170

1.5

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

-

-

-

-

-

-

1190

1.0

2.2

4.0

3.6

2.1

4.8

4.3

2.0

5.7

5.1

-

-

-

-

-

-

NOTES: 1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry indoor coil and no electric heat.

2. Refer to Page 12 for additional static resistances.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted
from the total static pressure of the blower.

*

Do

NOT close the pulley below 1 turn open.

** Factory setting.

511.06-N3Y