Table 11 - electrical data (basic units) – York SUNLINE 2000 B1CH240 User Manual

Page 14

background image

MODEL

POWER
SUPPLY

COMPRESSORS

OUTDOOR FAN

MOTORS

(#1 & #2)

SUPPLY AIR

BLOWER

MOTOR

MINIMUM

CIRCUIT

AMPACITY

(AMPS)

MAXIMUM

TIME DELAY

FUSE SIZE

(AMPS)

#1

#2

RLA LRA RLA LRA

HP

EACH

FLA

EACH

HP

FLA

B1CH180

208/230-3-60

28.2 260 28.2

260

1

4.1/4.2

5

14.4/15.4

86.1/87.3

110

460-3-60

14.1 128 14.1

128

1

2.1

5

7.2

43.1

50

575-3-60

11.5 104 11.5

104

1

2.0

5

5.9

35.9

45

B1CH240

208/230-3-60

33.3 300 33.3

300

1

4.1/4.2

7.5

19.4/21.0

102.6/104.4

125

460-3-60

19.2 146 19.2

146

1

2.1

7.5

9.7

57.2

70

575-3-60

12.8 124 12.8

124

1

2.0

7.5

7.8

40.6

50

*

Although these sizes are based on copper conductors, aluminum wire can be used.

Refer to the National Electric Code ( in U.S.A.) or the current Canadian Electrical Code
(in Canada) to determine the proper size.

TABLE 11 - ELECTRICAL DATA (BASIC UNITS)

VOLTAGE

LIMITATIONS**

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

630

**

Rated in accordance with ARI Standard 110, utilization range "A".

MODEL

B1CH

POWER
SUPPLY

HEATER OPTION

MINIMUM

CIRCUIT

AMPACITY

(AMPS)

MAXIMUM

TIME DELAY

FUSE SIZE

(AMPS)

MODEL

KW

1

STAGES

AMPS

180A25

208-3-60

E018
E036
E054
E072

13.5
27.0
40.6
54.1

1
2
2
2

37.5
75.1

112.6
150.1

133.0
133.0
179.9
179.9

150
150
200
200

230-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

43.3
86.6

129.9
173.2

141.4
141.4
195.5
195.5

150
150
200
200

180A46

460-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

21.7
43.3
65.0
86.6

70.2
70.2
97.3
97.3

80
80

100
100

180A58

575-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

17.3
34.6
52.0
69.3

57.5
57.5
79.2
79.2

60
60
80
80

240A25

208-3-60

E018
E036
E054
E072

13.5
27.0
40.6
54.1

1
2
2
2

37.5
75.1

112.6
150.1

149.5
149.5
196.4
212.7

150
150
200
225

230-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

43.3
86.6

129.9
173.2

158.5
158.5
196.4
212.7

175
175
200
225

240A46

460-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

21.7
43.3
65.0
86.6

84.2
84.2

111.3
111.3

90
90

125
125

240A58

575-3-60

E018
E036
E054
E072

18.0
36.0
54.0
72.0

1
2
2
2

17.3
34.6
52.0
69.3

62.3
62.3
83.9
83.9

70
70
90
90

1

Electric Heat CORRECTION FACTORS:

2

Although these sizes are based on copper conductors, aluminum wire can be used.

Refer to the National Electric code ( in U.S.A.) or the current Canadian Electrical Code
(in Canada) to determine the proper size.

TABLE 12 - ELECTRICAL DATA (UNITS w/SUPPLEMENTAL ELECTRIC HEAT)

NOMINAL VOLTAGE

VOLTAGE

KW CAP. MULTIPLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92