Service & maintenance – annual start-up, Check/test, Gold cga gas-fired water boiler — boiler manual – Weil-McLain Gold CGa User Manual

Page 48: Review with owner

background image

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

48

Part Number 550-101-009/0107

Service & maintenance – annual start-up

(cont.)

10b

Check/test

(continued)

Boiler relief valve

1. Inspect the relief valve and lift the lever to verify

flow as in the following warnings, excerpted from

a relief valve manufacturer’s warning label. Before

operating any relief valve, ensure that it is piped

with its discharge in a safe area to avoid severe scald

potential. Read manual Section

3

before proceeding

further.

. After following the above warning directions, if the

relief valve weeps or will not seat properly, replace

the relief valve. Ensure that the reason for relief valve

weeping is the valve and not over-pressurization of

the system due to expansion tank waterlogging or

undersizing.

Figure 27

Relief valve, typical

Review with owner

1. Review the

User’s Information Manual

with the

owner.

. Emphasize the need to perform the maintenance

schedule specified in the

User’s Information

Manual

(and in this manual as well).

3. Remind the owner of the need to call in a licensed

contractor should the boiler or system exhibit any
unusual behavior.

4. Remind the owner to follow the proper shutdown

procedure and to schedule an annual start-up at the
beginning of the next heating season.

Safety relief valves should be

reinspected AT LEAST ONCE

EVERY THREE YEARS

, by a

licensed plumbing contractor or

authorized inspection agency, to

ensure that the product has not

been affected by corrosive water

conditions and to ensure that the

valve and discharge line have not

been altered or tampered with

illegally. Certain naturally occur-

ring conditions may corrode the

valve or its components over time,

rendering the valve inoperative.

Such conditions are not detectable

unless the valve and its compo-

nents are physically removed and

inspected. This inspection must

only be conducted by a plumbing

contractor or authorized inspec-

tion agency — not by the owner.

Failure to reinspect the boiler

relief valve as directed could result

in unsafe pressure buildup, which

can result in severe personal in-

jury, death or substantial property

damage.

Following installation, the

valve

lever must be operated AT

LEAST ONCE A YEAR

to ensure

that waterways are clear. Certain

naturally occurring mineral de-

posits may adhere to the valve,

rendering it inoperative. When

manually operating the lever, wa-

ter will discharge and precautions

must be taken to avoid contact

with hot water and to avoid water

damage. Before operating lever,

check to see that a discharge line

is connected to this valve direct-

ing the flow of hot water from the

valve to a proper place of disposal

otherwise severe personal injury

may result.

If no water flows,

valve is inoperative.

Shut down

boiler until a new relief valve has

been installed.