For Your Safety

Tips for steam systems:

Check boiler and system piping for leaks.

Continual makeup water will reduce boiler life.

Minerals can build up in sections, reducing

heat transfer and causing cast iron to overheat,

resulting in section failure.

Failure to maintain recom-

mended pH and to repair leaks can cause

section iron corrosion, leading to section

failure and leaks. Do not use petroleum-

based sealing or stop-leak compounds in

boiler systems. Damage to system components

can result.

Boiler water pH 7.0 to 8.5 is recommended.

For pH conditions outside 7.0 to 8.5 range or

unusually hard water areas (above 7 grains

hardness), consult local water treatment

company.

Do not add cold water to hot boiler. Thermal

shock can cause sections to crack.

Clean newly installed steam boiler to remove

oil, grease, and other foreign material. Failure

to properly clean can result in violent water

level fluctuations, water passing into steam

mains, or high maintenance costs on strainers,

traps and and vents. A qualified service techni-

cian should skim the boiler by following

instructions on page 10 of this manual.

Follow instructions below to

prevent severe personal injury, death or substan-
tial property damage:

Do not use crankcase drainings or any oil

containing gasoline. See burner manual for

proper fuel oil.

Do not attempt to start burner when excess

oil has accumulated in combustion chamber,

when unit is full of vapor, or when combus

tion chamber is very hot.

Do not start burner unless collector hood, flue

cap, jacket cap, breeching and burner mount-

ing door are secured in place.

Never burn garbage or paper in the boiler.

Never leave combustible material around

boiler.

DO NOT TAMPER WITH UNIT OR CONTROLS.

Always follow specific instructions when

starting up boiler or performing routine

maintenance or service.

Follow instructions below to

prevent severe personal injury, death or substan-
tial property damage:

To avoid electric shock, turn off electrical

supply at switch on boiler and additional

external switches before performing service.

To avoid severe burns, allow boiler to cool

before performing service.

Do not block flow of combustion or ventilation

air to boiler.

Boiler must be connected to a flue with

sufficient draft at all times to assure proper

operation.

Do not use this boiler if any part has been

under water. Electrical and mechanical

failures may cause electric shock and fire

risks. Immediately call a qualified service

technician to inspect chimney or vent,

boiler and burner. Have the boiler flueways

cleaned and have the following replaced:

— all electrical and mechanical controls

— electrical wiring

— oil burner and controls

— insulation and chamber lining

Part No. 550-141-830/1202