Fuel Line Valves and Filter

Install two high quality oil duty rated shutoff valves

in accessible locations on the oil supply line. Locate
one close to the tank and the other close to the
burner, upstream of the fi lter.

Also install a generous capacity fi lter, rated for 50

microns or less, inside the building between the
fuel tank shutoff valve and the burner. Locate both
the fi lter and the valve close to the burner for ease
of servicing.

When installing an NX outside air adapter (Beck-

ett Part Number 5199OU), refer to the instruction
sheet supplied with the adapter. This kit allows
combustion air to be piped directly to the burner.
The NX outside air adapter kit may also be used
for chimney vent applications that require outside
combustion air.

Fuel Line Installation

Route the fuel line through the opening in the bottom

of the burner cover. Continuous lengths of heavy
wall copper tubing are recommended. Always use
fl are fi ttings. Never use compression fi ttings.

Always install fi ttings in accessible locations. To

avoid vibration noise, fuel lines should not run
against the appliance or ceiling joists.

Warning–Connect Outside
Air Duct to NX Adapter.

The outside air adapter must be installed by strictly
following the kit installation instructions. Do NOT attempt to
install outside air piping without using the outside air
adapter and instructions provided. Abundant fresh air is
required for proper combustion.

Failure to install adapter

properly could result in

impaired combustion,

appliance soot-up, puffback of

smoke, and fire or

asphyxiation hazards.

S121

!

Caution–Do Not Use

Teflon Tape

Never use Teflon tape on any fuel fitting. Tape
fragments can lodge in fuel line components and fuel
unit, damaging the equipment and preventing proper
operation.

Damage to the Pump could cause
impaired burner operation, oil
leakage and appliance soot-up.

S111

!

NOTICE

For protection in the event of fi re, some states

require the shutoff valves to be a fusible-handle
design. R.W. Beckett Corporation recommends
this design as good industry practice for all in-
stallations.