Burners with Beckett Clean Cut Pump must be used with a primary
control that has a valve-on delay (pre-purge). Controls shown have
valve on delay (see control manufacturer’s instructions for timings.)

Electrical shock hazard — can cause severe injury or death. Disconnect
power before installing or servicing.

120 VAC FIELD WIRING

LOW VOLTAGE FACTORY WIRING

120 VAC FACTORY WIRING

LOW VOLTAGE FIELD WIRING

SEE

BOILER

INSTRUCTION

MANUAL

FOR

CORRECT

WIRING

BURNER DISCONNECTS

120 VAC FIELD WIRING

LOW VOLTAGE FACTORY WIRING

120 VAC FACTORY WIRING

LOW VOLTAGE FIELD WIRING

Figure 4. – Typical Burner Wiring & Burner Sequence of Operation

1. STANDBY.

The burner is idle, waiting for a call for

heat. When a call for heat is initiated, there is a 2-6
second delay while the control performs a safe start
check.

2. VALVE-ON DELAY.

The ignition and motor are

turned on for a 15 second valve-on delay.

3.

TRIAL FOR IGNITION (TFI).

The fuel valve is

opened. A fl ame should be established within the
15 second lockout time.

4. LOCKOUT.

If fl ame is not sensed by the end of

the TFI, the control shuts down on safety lockout
and must be manually reset. If the control locks out
three times in a row, the control enters restricted
lockout.

5. IGNITION CARRYOVER.

Once fl ame is estab-

lished, the ignition remains on for 10 seconds to
ensure fl ame stability before turning off. If the con-
trol is wired for intermittent duty ignition, the ignition
unit stays on the entire time the motor is running.

6. RUN.

The burner runs until the call for heat is sati-

fi ed. The burner is then sent to burner motor off
delay, if applicable, or it is shut down and sent to
standby.

7. RECYCLE.

If the fl ame is lost while the burner is

fi ring, the control shuts down the burner, enters a 60
second recycle delay, and then repeats the above

ignition sequence. If fl ame is lost three times in a
row, the control locks out to prevent cycling with
repetitious fl ame loss due to poor combustion.

8. BURNER MOTOR-OFF DELAY.

The fuel valve

is closed and the burner motor is kept on for the
selected motor-off delay time before the control re-
turns the burner to standby.