Specifications, Hardwired models) – Tripp Lite 93-2007 (200106010) User Manual
Page 17

17
Specifications
(Hardwired Models)
HARDWIRED MODELS:
APSINT1524
APSINT2012
Weight:
12.7 Kg
17.1 Kg
INVERTER
Continuous power (@ 20° C):
1500 W
2000 W
Surge power (5 seconds):
3000 W
4000 W
Efficiency (Full Load):
89%
87%
Minimum DC Fuse Rating:
90A
370A
DC Input Current @ Nominal V DC
Full Load
70A
192 A
No Load
1.5A*
3 A*
Nominal Input Volts:
24 VDC
12 VDC
DC Input Voltage Range:
20-30 VDC
10-15 VDC
Nominal Output Volts:
230 VAC ±5%
230 VAC ±5%
Nominal Output Frequency:
50† Hz ±.3%
50† Hz ±.3%
BATTERY CHARGER
Charging Capacity DC:
10 A**
60 A
Maximum Cable Length
7 ft.
1 ft.
Acceptance Volts VDC:
Selectable
Selectable
28.8 V**/28.4 V Wet**/Gel
14.4 V**/14.2 V Wet**/Gel
Float Volts VDC (w/gel):
26.6 V (27.2 V)
13.3 V (13.6 V)
Input Voltage AC:
230 V
230 V
Input Current AC:
2.2 A**
7.0 A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 144**, 163, 182 or 201 VAC Selectable 144**,163, 182 or 201 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Selectable 259** or 264 VAC
Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
13.0 A
16 A
Input Frequency:
50 Hz ±10%
50 Hz ±10%
Maximum Output AC (Continuous)
6.5 A
8.7 A
Automatic Transfer Time:
4-6 ms
4-6 ms
HARDWIRED MODELS (Cont.):
APSINT2424
APSVRI3636
Weight:
18.5 Kg
25.6 Kg
INVERTER
Continuous power (@ 20° C):
2400 W
3600 W
Surge power (5 seconds):
4800 W
7200 W
Efficiency (Full Load):
89%
88%
Minimum DC Fuse Rating:
220A
130A
DC Input Current @ Nominal V DC
Full Load
112 A
114 A
No Load
1.8 A*
2 A*
Nominal Input Volts:
24 VDC
36 VDC
DC Input Voltage Range:
20-30 VDC
30-45 VDC
Nominal Output Volts:
230 VAC ±5%
230 VAC ±5%
Nominal Output Frequency:
50† Hz ±.3%
50† Hz ±.3%
BATTERY CHARGER
Charging Capacity DC:
30 A
30 A
Maximum Cable Length
3 ft.
4.5 ft.
Acceptance Volts VDC:
Selectable
Selectable
28.8 V**/28.4 V Wet**/Gel
43.2 V**/42.6 V Wet**/Gel
Float Volts VDC (w/gel):
26.6 V (27.2 V)
39.9 V (40.8 V)
Input Voltage AC:
230 V
230 V
Input Current AC:
7.0 A
10.4 A
LINE VAC OPERATION
Minimum Input AC Volts:
Selectable 144**,163, 182 or 201 VAC
Selectable 144**,163, 182 or 201 VAC
Maximum Input AC Volts
(Continuous, Charger at Maximum):
Selectable 259** or 264 VAC
Selectable 259** or 264 VAC
Maximum Input Current
(Continuous, Charger at Maximum):
17.0 A
26.0 A (30.0 A***)
Input Frequency:
50 Hz ±10%
50 Hz ±10%
Maximum Output AC (Continuous)
10.4 A
15.7 A
Automatic Transfer Time:
4-6 ms
4-6 ms
*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming
current.†A technician may be able to convert your UPS to receive 60 Hz ±10%power. Consult Tripp Lite for details.
200106010 230V APS Owners Manual.qxd 1/3/02 5:18 PM Page 17