beautypg.com

Service, Maintenance troubleshooting – Tripp Lite APSX Series User Manual

Page 11

background image

11A

Service

If you are returning your Inverter/Charger to Tripp Lite, please pack it carefully, using the ORIGINAL PACKING MATERIAL that came
with the unit. Enclose a letter describing the symptoms of the problem. If the Inverter/Charger is within the warranty period, enclose a copy
of your sales receipt. To obtain service you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an author-
ized Tripp Lite service center.

Your Inverter/Charger requires no maintenance and contains no user-serviceable or replaceable parts, but should be kept dry at all times.
Periodically check, clean and tighten all cable connections as necessary, both at the unit and at the battery.

Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service before returning
your unit for service.

Maintenance

Troubleshooting

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output

Unit is not properly connected to utility power.

Connect unit to utility power.

(All Indicator Lights Are OFF)

Operating Mode Switch is set to “OFF” and

Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY.”

AC input is present.

This is normal when the Operating Mode Switch

No correction is required. AC output will return when AC input

is set to “CHARGE ONLY” and AC input is absent.

returns. Set Operating Mode Switch to “AUTO/REMOTE” if you
require AC output.

Circuit breaker is tripped.

Reset circuit breaker.

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating

battery damage). The problem may be with connected

Mode Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE”

auxiliary chargers, if any, or with the unit’s charger.

or “CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Unit has shut down due to excessive battery discharge.

Use an auxiliary charger* to raise battery voltage. Check external
battery connections and fuse. Unit automatically resets when
condition is cleared.

Unit has shut down due to overload.

Reduce load. Reset by moving Operating Mode Switch to “OFF.”
Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”

Battery Not Recharging

Connected batteries are dead.

Check and replace old batteries.

(AC Input Present)

Battery fuse* is blown.

Check and replace fuse.*

Battery cabling* is loose.

Check and tighten or replace cabling.*

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

battery damage). The problem may be with connected

Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” or

auxiliary chargers, if any, or with the unit’s charger.

“CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Input circuit breaker is tripped.

Reset circuit breaker.

All Three Battery Indicator Lights

Battery is excessively discharged.

Use an auxiliary charger* to raise battery voltage. Check external

Are Slowly Flashing

battery connections and fuse. Unit automatically resets when

(½ Second Flashes)

condition is cleared.

All Three Battery Indicator Lights

Battery is overcharged. Unit will shut down to prevent

Disconnect any auxiliary chargers. Reset by moving Operating Mode

Are Rapidly Flashing

battery damage. The problem may be with connected

Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE”

(¼ Second Flashes)

auxiliary chargers, if any, or with the unit’s charger.

or “CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Red “LOW” Battery

Battery voltage is low. Unit will automatically shut down

Make sure that AC power is present in order to recharge batteries.

Indicator Light is Flashing

after 5 seconds to protect battery from damage.

Reset by moving Operating Mode Switch to “OFF then to
“AUTO/REMOTE” or “CHARGE ONLY.”

False reading due to undersized or insufficiently connected

Use sufficient size DC cable sufficiently connected to the

DC cabling.

Inverter/Charger.

Red “LOAD” Operation

Inverter is overloaded. Unit will automatically shut down

Reduce load. Reset by moving Operating Mode Switch to “OFF.”

Indicator Light Flashing

after 5 seconds.

Wait 1minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”

* User-supplied.

Battery Indicator Lights

Operating Mode Switch

Operation Indicator Lights

Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with
all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model
number of the product.

200608120 93-260

8 230V APS OM.qxd 10/16/2006 10:46 AM Page 11

This manual is related to the following products: