beautypg.com

Integrated enclosure & extender box, Integrated enclosure, Extender box – Toshiba Q9 Series User Manual

Page 5

background image

Toshiba allows you to “build your own drive” by including many of the popular features
requested by the HVAC market as choices for your own standard package. The
configurations you can choose include line reactors for input power-conditioning and
harmonic mitigation, as well as the choice between two or three-contactor bypasses to
allow for across-the-line motor operation.

Integrated Enclosure

& Extender Box

* Height does not include power unit dimension.

Bypass Box Dimensions

Without Reactor

With Reactor

230 V

30 HP

40 HP

-

30 HP

40 HP

460 V

-

50 to 100 HP

50 to 60 HP

-

75 to 100 HP

Height (in.)*

35.5

36.3

36.3

40.5

41.3

Width (in.)

16.0

16.0

16.0

16.0

16.0

Depth (in.)

12.5

12.5

12.5

12.5

12.5

Integrated Enclosure Dimensions

Without Reactor

230 V

3 to 7.5 HP

10 to 25 HP

460 V

3 to 15 HP

20 to 40 HP

Height (in.)

28.5

45.5

Width (in.)

16.1

16.1

Depth (in.)

10.6

13.9

Integrated Enclosure

“Build your own drive” uses a
standard NEMA 1 enclosure
that is available with the
following options:

Input Circuit Breaker

Two-Contactor Bypass

Three-Contactor Bypass

3% AC Line Reactor

5% AC Line Reactor

DC Link Reactor

Extender Box

The extender box includes the
same options for line reactors
and bypass configurations as
the integrated enclosure. The
extender box is connected to
the bottom of the standard
Q9 power unit, and the entire
assembly is NEMA 1 rated.