1600XP Series Quick Installation Guide

When operating in the inverter mode, placing the breaker in the

OFF position will switch the UPS to the

battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be

in the bypass mode at the time that the breaker is placed in the

OFF position for the UPS to shutdown

power to the load.
Wait at least 5 minutes after an Emergency Power Off (EPO) before resetting the UPS breaker. This

allows the UPS circuitry to fully discharge. The UPS could be damaged if the unit is not fully discharged

before the breaker is reset.

Hardwire Connections

Remove the terminal cover plate on the lower-left back side of the UPS. Follow the directions below in wiring the unit.

Jumper Position for 208V/240V Input, 240/208/120V Output

Jumper Position for 230V Input, 230V Output

NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with the provided jumper wire/bus bar. DO NOT jumper terminal 13 to

12 or 11. Factory Setting is 208Vac.

Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.

NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with the provided jumper wire/bus bar. DO NOT jumper terminal 11 to

12 or 13.

Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.

NOTE 3 – 8-22 kVA UPSs have a jumper bus bar.

Output Terminal Connections

Connect the load to the output terminals according the load voltage requirements. See
the Output Terminal Voltages table to the right.

Wire Size and Tightening Torque

Use the following table to select the recommended wire size and terminal lug

tightening torque for I/O wire connections.

Item

Terminal

Number

AWG

3.6 kVA

AWG

6 kVA

AWG

8 kVA

AWG

10 kVA

AWG

14-18 kVA

AWG

22 kVA

Tightening Torque

lb.-in. (N•m)

AC Input Lines

1 and 2

12 (8)

10

(8)

8

(1/0)

6

(1/0)

4

(1/0)

1

(1/0)

14.2 (1.56)

AC Output Lines

4, 5, and 7

12 (8)

10

(8)

8

(1/0)

6

(1/0)

4

(1/0)

1

(1/0)

14.2 (1.56)

AC Output Neutral

6

12 (8)

10

(8)

8

(1/0)

6

(1/0)

4

(1/0)

1

(1/0)

14.2 (1.56)

Ground

3 and 8

12 (8)

10

(8)

8

(1/0)

6

(1/0)

4

(1/0)

1

(1/0)

14.2 (1.56)

EPO Switch

14 and 15

16

16

16

16

16

16

9.0 (0.99)

Remote Switch

16 and 17

16

16

16

16

16

16

9.0 (0.99)

Note: Wire size presented as the recommended size followed by a bold number in () that is the maximum wire size the terminal block can
accommodate. See the manual, page 48, for knock-out hole sizes on the back of each model.

3

NOTICE

Output Terminal Voltages

Vout

Terminal Lugs

120 V

X3 - N, X1 - N

208 V

X3 - X2

240 V

X3 - X1

230 V

X3 - X1

Jumper

position

for 208 V

120 V

208/240 Vin

REMOTE1

208

EPO2

EPO1

REMOTE2

COM 240

G

X3

1

L2

G

X1

X2

N

2

3

12

14

13

15

8

7

6

5

11

4

16 17

L1

120 V

208 V

240 V

Jumper

position

for 240 V

230 Vin

REMOTE1

EPO2

EPO1

REMOTE2

G

X3

1

L2 (N)

G

X1

X2

N

2

3

12

14

13

15

8

7

6

5

11

4

16 17

L1 (L)

230 V