Instruction codes – Toshiba TOSVERT VF-S15 series option unit Function E6581830 User Manual
Page 29

E658130
- 28 -
5.5.8. Instruction Codes
Code No.
Item
Description
1003H
Command mode selection
read
2003H
Command mode selection
write
0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: No function
4: Communication option
1004H
Frequency setting mode
selection read
2004H
Frequency setting mode
selection write
0: Setting dial 1(save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: No function
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro
0072H Special
monitor
0000H to FFFFH:
Monitor value selected after choosing instruction code 00F3H.
read 0073H Special monitor code read
Read the content that was monitored by special monitor.
write 00F3H Special monitor selection
Select the monitor code of special monitor.
0074H
Trip history No.1, No.2 read
Read the No.1 and No.2 of trip information.
0075H
Trip history No.3, No.4 read
Read the No.3 and No.4 of trip information.
0076H
Trip history No.5, No.6 read
Read the No.5 and No.6 of trip information.
0077H
Trip history No.7, No.8 read
Read the No.7 and No.8 of trip information.
006DH
Frequency command value
(RAM) read
Read the frequency command value (RAM).
00EDH
Option frequency command
value (EEPROM&RAM) write*
Write the option frequency command value (EEPROM &RAM).
00F4H
Trip history clear
9696H: Clear all trip histories.
00FCH
Parameter all clear
9696H: Clear all parameters. (Parameters other than
proofreading values are made into factory default settings.)
00FDH
Inverter reset
9696H: Reset the inverter.
1000H to 1999H
(1000H to
1F99H)
Read parameters (RAM)
To read parameters f000 to f984, add the triple figures
that follow Fxxx to 1000H.
(Ex: f984 -> 984 + 1000 = 1984)
No error occurs when you select 1A00 to 1F99.
Because these parameters are for maintenance.
2000H to 2999H
Write parameters
(EEPROM&RAM) *
To write parameters f000 to f984, add the triple figures
that follow Fxxx to 2000H.