True food service equipment, inc, Installation / operation instructions, Wire gauge for 2% voltage drop in supply circuits – True Manufacturing Company TMC-34-SS User Manual
Page 9

............ www.truemfg.com ............
True Food Service Equipment, Inc.
7
7
INSTALLATION / OPERATION INSTRUCTIONS
115 Volt
Amps
20
30
40
50
60
70
80
90
100
120
140
160
Distance in Feet to Center of Load.
Wire Gauge for 2% Voltage Drop in Supply Circuits
2
3
4
5
6
7
8
9
10
12
14
16
18
20
25
30
35
40
45
50
14
14
14
14
14
14
14
14
14
14
14
14
14
14
12
12
10
10
10
10
14
14
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
14
14
14
14
14
14
14
12
12
12
10
10
10
10
8
8
6
6
6
6
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
6
6
5
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
6
5
5
4
14
14
14
14
12
12
12
10
10
10
8
8
8
8
6
6
5
5
4
4
14
14
14
12
12
12
10
10
10
8
8
8
8
6
6
6
5
4
4
3
14
14
14
12
12
10
10
10
10
8
8
8
8
6
6
5
4
4
3
3
14
14
12
12
10
10
10
8
8
8
6
6
8
6
5
4
4
3
3
2
14
14
12
10
10
10
8
8
8
8
6
6
8
5
4
4
3
2
2
1
14
12
12
10
10
8
8
8
8
6
6
6
5
5
4
3
2
2
1
1
230Volt
Amps
20
30
40
50
60
70
80
90
100
120
140
160
Distance in Feet to Center of Load.
Wire Gauge for 2% Voltage Drop in Supply Circuits
5
6
7
8
9
10
12
14
16
18
20
25
30
35
40
50
60
70
80
90
100
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
12
12
10
10
10
10
14
14
14
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
14
14
14
14
14
14
14
14
14
14
14
12
12
10
10
10
8
8
8
6
6
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
6
6
6
6
6
14
14
14
14
14
14
14
14
12
12
10
10
10
10
8
6
6
6
6
5
5
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
6
6
6
5
5
4
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
5
5
4
4
14
14
14
14
14
12
12
12
10
10
10
10
8
8
6
6
6
5
4
4
3
14
14
14
14
12
12
12
10
10
10
10
8
8
8
6
6
5
5
4
3
3
14
14
14
12
12
13
10
10
10
8
8
8
6
6
6
5
4
4
3
3
2
14
14
12
12
12
10
10
10
8
8
8
6
6
6
5
4
4
2
2
1
1
14
12
12
12
10
10
10
8
8
8
8
6
6
5
5
4
3
2
2
1
1