Separate vent kit installation – QHT Boiler User Manual
Page 15

Separate Vent Kit Installation
Figure 1
Figure 2
Termination Location / Installation: 
Drill the intake and exhaust holes through the 
external wall according to the boiler mounting 
diagram supplied in the boiler package. Be 
sure to account for the 3° downward pitch 
away from the boiler as shown in Figure 1. 
 
Termination Installation : 
Install the intake (H) and exhaust (D) 
terminations through the corresponding 
exterior walls as shown in Figure 3. Slide the 
wall gaskets (C) onto each of the pipes to 
secure the pipe against the wall. 
Figure 4
15
Exhaust Collar Installation : 
Mount the exhaust gasket (K) on the exhaust 
outlet of the boiler as shown in Figure 4. 
Install the appropriate flue restrictor ring (L) 
according to the table on page ?. Secure the 
Exhaust Collar (J) to the top of the boiler using 
the 4 screws (G) supplied. 
Figure 3
3° Downward pitch 
(2” per 39” length). 
Away from boiler
3° Downward pitch 
(2” per 39” length). 
Away from boiler
Gasket Installation: 
Install the gaskets (E) in the exhaust and 
intake boiler collars (I,J) and elbows (F), as 
shown in figure 2. 
 
