A. Fitting Selection:

Check the switch part number

to determine the required fitting mount size and
thread type. The switch is commonly installed in
tank adapters, flanges, brackets or stand pipes.

1. Adapter:

Select a tank adapter fitting with

minimal height so as to ensure that the
installed transducer will not be substantially
elevated into the fitting. Avoid tank adapter
styles with threads and/or pipe stops forward
of the installed transducer.

2. Flange:

Tall flanges with narrow risers

impede the acoustic signal. Select a fitting
with the right riser height versus inner diame-
ter geometry. The switch may be elevated up
to 12” (30 cm) in a 6” (15 cm) riser, 8” (20
cm) in a 4” (10 cm) riser and 3” (7.6 cm) in a
2” (5 cm) riser.

3. Bracket:

A LVM-30 side mount bracket or

equivalent can be used for open tank top
installations against the side wall.

4. Stand Pipe:

A stand pipe may be

used to dampen turbulence or separate
surface foam. Select a 2” or larger
pipe for model LVCN704/709. Select
a 3” or larger pipe for model
LVCN716/726. The pipe length
should run the measurement span. Cut
a 45° notch at the bottom of the pipe
and drill a 1/4” pressure equalization
hole high in the dead band.

Step Thirteen

INSTALLATION

Adapter

VACUUM

Do not install at

angle relative

to the liquid

Do not install with-

in 3” of

tank side wall

Do not install

with objects

in the beam

Do not install

in applications

with vacuum

Warning

Install the appropriate installation fitting. Make sure that
the fitting and switch threads are not damaged or worn.
Install the switch with the included Viton mounting gasket.
Hand tighten the switch within the fitting. Perform an
installed leak test under normal process conditions prior to
system start up.

Gasket

Flange

on Riser

Height

Inner Diameter

Riser

Bracket

Stand Pipe

Dead Band

Ventilation
Hole

Operational Range

Highest
Liquid Level

Lowest
Liquid Level

2"/3" Minimum
Diameter

Step Twelve

PROGRAMMING

12. Press the HIGH button for the first key-stroke and the Relay LED

will blink once.

13. Press the HIGH button again for the second key-stroke and the

Relay LED will blink twice.

14. The Power LED will flash from AMBER to GREEN when the set

point has been accepted into memory.

15. Press the SELECT switch repeatedly until BOTH LEDs for Relay

1 and Relay 2 are ON (after Relay 3).

16. Press the HIGH button for the first key-stroke and Relay LED will

blink once.

17. Press the HIGH button again for the second key-stroke and Relay

LED will blink twice.

18. Press SELECT to program the next relay channel or slide the

RUN/CAL switch RIGHT to exit the CAL mode.

Note: The duplexing mode can be disabled by repeating Steps #15-18
and pressing the LOW button instead of the HIGH button in the
HIGH/HIGH combination.

Programming Alternating Control Only:

1. To program the switch for alternating

control only without the lead-lag func-
tion, follow the instructions for
Programming Duplexing Pump Control
(Steps 11 and 12). The difference
between Duplexing and Alternation is
the location of the Relay 2 set point. Set
Relay 2 close to the deadband without
crossing into the deadband and above
the highest level of expected liquid.

Note: The alternation mode can be disabled
by repeating Steps #15-18 and pressing the
LOW button instead of the HIGH button in the HIGH/HIGH combi-
nation.

Duplex Programming

(Backup)

Box

Insert

Table

Target

Wall

Tape

Distance

Set Point

De-energize (All) Low

Energize

High

High High

Alternating

11

Alternating Programming

(Backup)

Box

Insert

Table

Target

Wall

Tape

Distance

Set Point

2

Programming Duplex Pump Control (continued):