Programming – Omega Vehicle Security LVCN700 Series User Manual

Page 6

background image

Step Eight

PROGRAMMING

Step Nine

PROGRAMMING

C. Programming a High and Low Level Out of Bounds
Alarm:

After having powered the switch with the appropriate supply

voltage, entered the CAL mode, selected a relay channel and erased

any previously input set points, follow the below procedure:

1. Stretch the tape measurer out to the appropriate distance in

between the switch and target.

2. Position the switch at the desired HIGH

set point distance defined as the lesser

of the two air gap spaces between the

transducer and the target. Make sure

that the switch is stationary and per-

pendicular to the target before con-

tinuing.

3. Press the HIGH button for the first key-

stroke and the Relay LED will blink

once.

4. Press HIGH again for the second key-stroke and the Relay LED

will blink twice.

5. The Power LED will flash from AMBER to GREEN when the

HIGH set point has been accepted into memory.

6. Position the switch at the desired LOW set point distance defined

as the greater of the two air gap spaces between the transducer and

the target. Make sure that the switch is stationary and perpen-

dicular to the target before continuing.

7. Press LOW for the first key-stroke and the Relay LED will blink

three times.

8. Press LOW for the second key-stroke and the Relay LED will

blink four times.

9. The Power LED will flash from AMBER to GREEN when the

LOW set point has been accepted into memory.

10. Press SELECT to program the next relay channel or slide the

RUN/CAL switch RIGHT to exit the CAL mode.

Box

Insert

Table

Target

Wall

Tape

High and Low Level

Out of Bounds Alarm Programming

High

Set Point

Distance

Low

Set Point

Distance

Energize

Energize

De-energize

Out of Bounds

D. Programming Automatic Fill:

After having powered the

switch with the appropriate supply voltage, entered the CAL mode,

selected a relay channel and erased any previously input set points,

follow the below procedure:

1. Stretch the tape measurer out to the appropriate distance in

between the switch and target.

2. Position the switch at the desired LOW

set point distance defined as the greater

of the two air gap spaces between the

transducer and the target. Make sure

that the switch is stationary and per-

pendicular to the target before con-

tinuing.

3. Press the LOW button for the first key-

stroke and the Relay LED will blink

once.

4. Press the HIGH button for the second key-stroke and the Relay

LED will blink twice.

5. The Power LED will flash from AMBER to GREEN when the

LOW set point has been accepted into memory.

6. Position the switch at the desired HIGH set point distance defined

as the lesser of the two air gap spaces between the transducer and

the target. Make sure that the switch is stationary and perpen-

dicular to the target before continuing.

7. Press the HIGH button for the first key-stroke and the Relay LED

will blink three times.

8. Press the LOW button for the second key-stroke and the Relay

LED will blink four times.

9. The Power LED will flash from AMBER to GREEN when the

HIGH set point has been accepted into memory.

10. Press SELECT to program the next relay channel or slide the

RUN/CAL switch RIGHT to exit the CAL mode.

Energize

De-energize

Automatic Fill

Box

Insert

Table

Target

Wall

Tape

Automatic Fill

Programming

High

Set Point

Distance

Low

Set Point

Distance

6

2

2