Programming – Omega Vehicle Security LVCN700 Series User Manual
Page 6
Step Eight
PROGRAMMING
Step Nine
PROGRAMMING
C. Programming a High and Low Level Out of Bounds
Alarm:
After having powered the switch with the appropriate supply
voltage, entered the CAL mode, selected a relay channel and erased
any previously input set points, follow the below procedure:
1. Stretch the tape measurer out to the appropriate distance in
between the switch and target.
2. Position the switch at the desired HIGH
set point distance defined as the lesser
of the two air gap spaces between the
transducer and the target. Make sure
that the switch is stationary and per-
pendicular to the target before con-
tinuing.
3. Press the HIGH button for the first key-
stroke and the Relay LED will blink
once.
4. Press HIGH again for the second key-stroke and the Relay LED
will blink twice.
5. The Power LED will flash from AMBER to GREEN when the
HIGH set point has been accepted into memory.
6. Position the switch at the desired LOW set point distance defined
as the greater of the two air gap spaces between the transducer and
the target. Make sure that the switch is stationary and perpen-
dicular to the target before continuing.
7. Press LOW for the first key-stroke and the Relay LED will blink
three times.
8. Press LOW for the second key-stroke and the Relay LED will
blink four times.
9. The Power LED will flash from AMBER to GREEN when the
LOW set point has been accepted into memory.
10. Press SELECT to program the next relay channel or slide the
RUN/CAL switch RIGHT to exit the CAL mode.
Box
Insert
Table
Target
Wall
Tape
High and Low Level
Out of Bounds Alarm Programming
High
Set Point
Distance
Low
Set Point
Distance
Energize
Energize
De-energize
Out of Bounds
D. Programming Automatic Fill:
After having powered the
switch with the appropriate supply voltage, entered the CAL mode,
selected a relay channel and erased any previously input set points,
follow the below procedure:
1. Stretch the tape measurer out to the appropriate distance in
between the switch and target.
2. Position the switch at the desired LOW
set point distance defined as the greater
of the two air gap spaces between the
transducer and the target. Make sure
that the switch is stationary and per-
pendicular to the target before con-
tinuing.
3. Press the LOW button for the first key-
stroke and the Relay LED will blink
once.
4. Press the HIGH button for the second key-stroke and the Relay
LED will blink twice.
5. The Power LED will flash from AMBER to GREEN when the
LOW set point has been accepted into memory.
6. Position the switch at the desired HIGH set point distance defined
as the lesser of the two air gap spaces between the transducer and
the target. Make sure that the switch is stationary and perpen-
dicular to the target before continuing.
7. Press the HIGH button for the first key-stroke and the Relay LED
will blink three times.
8. Press the LOW button for the second key-stroke and the Relay
LED will blink four times.
9. The Power LED will flash from AMBER to GREEN when the
HIGH set point has been accepted into memory.
10. Press SELECT to program the next relay channel or slide the
RUN/CAL switch RIGHT to exit the CAL mode.
Energize
De-energize
Automatic Fill
Box
Insert
Table
Target
Wall
Tape
Automatic Fill
Programming
High
Set Point
Distance
Low
Set Point
Distance
6
2
2