Clear interrupt, The analog input selection register, 6 clear interrupt – Omega 1002 User Manual
Page 32: 7 the analog input selection register

3.2.2.6 Clear Interrupt
Reading from 1Ch will clear the add-on interrupt.
3.2.2.7 The Analog Input Selection Register
The analog input channel selection register uses address 10h and
address 14h is used by the analog gain control selection register. Write 0-31 to
port 10h to select the channel number (for differential input, write 0-15).
Write 0-3 to port 14h to select the gain control.
Figure 3-2. Analog input control.
Note:
1. For single ended inputs, channels 0-31 are available. For
differential inputs, channels 0-15 are available. If you enter a
channel number greater than the number available, those channels
will be ignored. Thus, for single-ended inputs, only the last 5 bits
are taken as the channel number. And for differential inputs, only
the last 4 bits are taken as the channel number.
2. Only the last two digits are used as the gain control code. The gain
control codes and corresponding gains are shown below :
For OME-PCI-1002L:
Gain code
[0 0]
[0 1]
[1 0]
[1 1]
Gain 1
2
4 8
…
Analog inputs
…
Channel select
Analog
Mux.
Select
Gain control
ADC
AMP
32