MOUNTING

On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents,

do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator

to the side of the vent.

The vent damper is set up for a continuous pilot system. If the vent damper is installed on an Intermittent Pilot

or Hot Surface Ignition equipped system, the energy savings of the vent damper can be improved by plugging the

hole in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.

Hole in Vent Damper Blade

Closed Position

Fig. #8994

DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a

hazardous condition.

Fig. #8183.0

INSTALLING THE VENT DAMPER IN HORIZONTAL

& VERTICAL VENTS.

Fig. #152323

D80D GENERAL WIRING DIAGRAM

INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON

MONOXIDE POISONING, COULD RESULT.

1K

1K1

1K2

D80
MOTOR

N.C.

END
SWITCH

N.O.

1K3

C.

4

3

2

1

YELLOW

BLUE

BLACK

ORANGE

CABLE

NO

YES

NO

YES

INSTALL VENT

DAMPER WITH

ACTUATOR TO SIDES

OF VENT ONLY. DO

NOT MOUNT ABOVE OR

BELOW VENT.

TO CHIMNEY

TO BOILER

VENT DAMPER

FLOW >

HORIZONTAL INSTALLATION

TO CHIMNEY

AT BOILER

DRAFT

HOOD

VENT

DAMPER

VERTICAL

INSTALLATION

ACTUATOR MAY BE

INSTALLED IN ANY

POSITION ON VERTICAL

PIPE.