beautypg.com

Power supply wiring and grounding, 2 power supply wiring and grounding – RuggedCom RS416 User Manual

Page 15

background image

Installation

15

RuggedCom

®

RuggedServer™ RS416 Family Installation Guide rev118

2.2 Power Supply Wiring and Grounding

The RS416 supports dual redundant power supplies – “Power Supply 1 (PS1)” and
“Power Supply 2 (PS2)”. RS416P features a universal high voltage range power supply
as PS1, and a separate 48VDC supply, PS2, to provide Power over Ethernet. The
connections for PS1, PS2 and the fail-safe relay are located on the terminal block as
shown in Figure 6 and Figure 7.

Figure 6: RS416 Series Phillips Screw Terminal Block

Figure 7: RS416 Series Phoenix Plug Terminal Block

The RS416 Family chassis ground connection, shown in Figure 8, uses a #6-32 screw. It
is recommended to terminate the ground connection in a #6 ring lug, and to use a torque
setting not exceeding 15 in.lbs (1.7 Nm).

Figure 8: Chassis Ground Connection

The RS416 can be equipped with either a Phillips Screw Terminal Block or a Phoenix
Plug Terminal Block. The Phillips Screw Terminal Block has Phillips screws with a

#6-32 screw with
ext. washer.

#6 ring lug

stainless steel standoff

Philips Screw Terminal without Cover

Philips Screw Terminal with Cover

Safety Cover

Safety Cover

Screws

Chassis Ground

Connection

Surge / Chassis

Ground Jumper

Terminal

Phoenix Plug Terminal without Cover

Phoenix Plug Terminal with Cover

Safety Cover

Screws

Safety Cover

Chassis Ground

Connection

Terminal

Surge / Chassis

Ground Jumper