Installation, Rigid pipe venting systems, Horizontal or vertical terminations – Regency Panorama P36D User Manual
Page 24
FPI P36D-1 Zero Clearance Direct Vent Gas Fireplace
24
Rigid Pipe Adaptor
Pipe Length
Vertical
Termination
Cap
Storm Collar
Flashing
Ceiling Firestop
24" Pipe
Length
Adj.Pipe Length
11" - 14-5/8"
90 Elbow
o
Horizontal
Termination
Cap
Wall Thimble
Vinyl Siding
Standoff (Optional)
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
The minimum components required for a basic
horizontal termination are:
1 Horizontal
Termination
Cap
1 90
o
Elbow
1 Rigid
Pipe
Adaptor
1 Wall
Thimble
1 Length of pipe to suit wall thickness
(see
chart)
Wall thickness is measured from the back standoffs
to the inside mounting surface of termination cap.
For siding other than vinyl furring strips may be used,
instead of the vinyl siding standoff, to create a level
surface to mount the vent terminal. The Terminal
must not be recessed into siding. Measure the wall
thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used
with vinyl siding), measure to outside surface of wall
without siding and add 2 inches.
The FPI AstroCap
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent
®
Direct Vent GS,
American Metal Products, Security Secure Vent
®
, AmeriVent Direct Vent. AstroCap
TM
is the proprietary trademark of FPI Fireplace Products International
Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
This product has been evaluated by Intertek
for using a Rigid Pipe Adaptor in conjunction
with DuraVent Direct Vent GS, Selkirk Direct-
Temp, Ameri Vent Direct venting and Security
Secure Vent systems. Use of these systems with
the Rigid Pipe Adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.
WARNING:
Do not combine venting components from
different venting systems.
However use of the AstroCap
TM
and FPI Riser
is acceptable with all systems.
Flat Wall Installation
Wall Thickness (inches)
Vent Length Required (inches)
4" - 5-1/2"
6"
7" - 8-1/2"
9"
10" - 11-1/2"
12"
9" - 14-1/2"
11" - 14-5/8" Adj. Pipe
15" - 23-1/2"
17" - 24" Adj. Pipe
Corner Installation
Wall Thickness (inches)
Vent Length Required (inches)
3-1/4" - 6-3/4"
11" - 14-5/8" Adj. Pipe
7-3/4" - 16-1/4"
17" - 24" Adj. Pipe
7-1/4" - 8-3/4"
6" + 12"
9" + 9"
4-1/4" - 5-3/4"
6" + 9"
Alternate
Horizontal
Termination
Caps
INSTALLATION